Items | Parameters | ||
Rated output power | 600W (Note: Please use the constant speakers within the power range) | ||
Rated output voltage | 100V | ||
Sensitivity | MIC | 5mv(±1mv) | |
AUX IN | 1VRMS(±100mv) | ||
SNR | MIC | ≥70dB | |
AUX IN | ≥80dB | ||
Frequency response | MIC | 100Hz~10KHz(±3dB) | |
AUX IN | 80Hz~15KHz(±3dB) | ||
Ratio of source emf. | ≥12dB | ||
THD | ≤1>#/p### | ||
Tone adjustment range | ±11±2 dB | ||
Rated power consumption | 850W | ||
AC-DC power supply switching time | No interruption | ||
12AH battery (two batteries in series into 24V) endurance | 2H (normal emergency voice broadcast) | ||
Battery | Size | (2 pcs) | |
Voltage | 12V; (two in series into 24V) | ||
Working Voltage | AC220V-230V/50Hz | ||
Package dimensions | 820×470×275mm | ||
Machine dimensions | 750×400×180mm | ||
Gross weight | 20kg | ||
Net weight | 19kg(without batteries) | ||
ტექნიკური დეტალები
Digital display screen to display time, system status, and Fireman MIC status;
● One-key alarm and two kinds of editable EVAC messages; EMC microphone for on-site voice evacuation;
● With LED light for indicating system connection status and fault status;
● Support speaker line detection (light load, over load and short circuit);
● LED display to indicate the type of audio source of the current signal;
● 2 aux input interface, 1 Fireman MIC input, support offline detection; each paging record is automatically saved to SD card;
● Support AC power supply and 24V battery power supply; support automatically and seamlessly identify and convert. AC power supply is with the priority;
● Equipped with 24V battery charger, which can be charged automatically when the system is powered by AC;
● System error information is backed up by logging in SD card;
● A/B line speaker output for four zones; independent power switch and volume control for each zone; with master volume control, treble and bass adjustment; each channel can output 600W, and the total power of 4 zones need to be within 600W;
● 4-channel link relay output interfaces (can control the short circuit of two wires to control other equipment); 2 24V output interfaces give peripheral equipment 24V (not greater than 0.5A) input signal;
● 4 input dry contacts, which can be integrated with the third-party system (such as the fire alarm system) through the input of dry nodes;
● 2-bit network cable interface, used to connect PAVA4400FM fireman microphone and PAVA4600 extender;
● It has testing function keys with LED.